Say a room is warm and the fan icon is green on the building automation system (BAS). I’d start by finding out what turns that icon green. It might be the command asking the fan to run, the drive reporting it’s running, or a separate proof signal. Look at the points list or the graphic binding. Figuring out what that point reads can save you a trip to the wrong piece of equipment.
Then I’d pull up the trend for the time the room was warm. Put the air handler’s duct static pressure next to its setpoint. Look at the measured airflow and airflow setpoint for the variable air volume (VAV) box serving the room. If the air handler is holding pressure and the other boxes are getting their air, I’d spend more time looking at the box for that room.
Here’s a simple example. The box is calling for 400 cfm, and the graphic says it’s only getting 180. I’d check where that 180 came from before changing anything. Think about what you’d expect to see at the box itself, then compare it with what the workstation is showing.