The question on this one is simple: when can you turn the compressors off and still keep both loops where they need to be? A 60 MW reference design makes that question worth answering before the equipment list goes out.

Daikin Applied introduced its D60-W reference architecture on November 10 for data centers built around NVIDIA's DSX AI Factory platform. The design is sized for a 60 MW IT load across six modular units. Daikin assigns 92% of that load to liquid cooling and the rest to air cooling. A warmer water loop serves the coolant distribution units, and a separate cooler loop serves rack containment units that collect the remaining heat.

Daikin describes three operating modes. Dry coolers can reject heat with chiller compressors off when outdoor conditions permit. In hybrid operation, waterside economizers precool the returning water and chillers cover the balance. The plant can also run in full mechanical cooling. The reference design uses dry coolers in place of evaporative cooling towers, avoiding tower makeup water.

For a project team, the key question is how often the site can actually run each mode. Ask for an hourly estimate using local dry-bulb weather, the two loops' water-temperature requirements, and the expected rack mix. Compare combined chiller, pump, and fan energy across the year. During commissioning, verify the transition between modes under load and check what happens when a module goes out of service.

The announcement describes a design starting point. Daikin says its own coolant distribution unit and data center dry cooler are still in development, with availability targeted for the second half of 2027. A project with an earlier delivery date needs a confirmed equipment list and an agreed plan for any substitutions.

Put that question into the controls review, too. Ask who owns the changeover, what temperatures and trends the operator will see, and how the plant backs out if the cooler loop starts to drift. A sequence that works only on a sunny slide deck still has to survive the first real handoff.